Technical Details – Scott-T Transformer

1. Overview

A Scott-T transformer is a special type of transformer arrangement used to convert three-phase electric power into two-phase power, and vice versa. It is named after Charles F. Scott, who introduced this method for phase conversion.


2. Applications

  • Power supply to two-phase systems (e.g., older industrial machinery)
  • Traction systems (railways with two-phase motors)
  • Balancing unbalanced loads
  • Interfacing two-phase legacy systems with modern three-phase grids

3. Basic Configuration

A Scott-T transformer uses two single-phase transformers:

  • Main transformer
  • Teaser transformer

Connection Details:

  • The main transformer is connected between two phases (e.g., A and C) of a three-phase system.
  • The teaser transformer is connected from the third phase (B) to a tap on the main transformer winding (typically at 86.6% or √3/2 of the winding).

Voltage Ratios:

  • The teaser transformer's primary is 86.6% of the line voltage.
  • The teaser’s secondary must be equal in voltage to the main transformer’s secondary to ensure balanced two-phase output.

4. Technical Specifications

Parameter
Typical Value
Primary Voltage
3-phase, 50/60 Hz (e.g., 11 kV, 6.6 kV)
Secondary Voltage
2-phase output (e.g., 415 V-2Φ)
Frequency
50 or 60 Hz
Phase Shift
90° between two-phase outputs
Tap Position (Teaser)
50% to 86.6% from main’s neutral point (ideally at 0.866 × Vline)

5. Vector Representation

  • The two-phase outputs are electrically 90° out of phase, forming a balanced two-phase system.
  • The currents in the three-phase input remain balanced, if the two-phase loads are equal.

6. Design Considerations

  • Magnetic coupling between windings is critical for maintaining phase relationships.
  • Load balancing is important to avoid unbalanced current on the three-phase side.
  • Proper tapping on the main transformer ensures correct voltage and phase angle.

7. Advantages

  • Simple and cost-effective method for phase conversion.
  • Allows integration of two-phase systems with standard three-phase grids.
  • Provides balanced loading on the three-phase supply when used correctly.

8. Limitations

  • Limited to specific use cases where two-phase supply is needed.
  • Requires careful design to maintain voltage balance and phase angle.
  • Less commonly used today due to the decline of two-phase systems.

9. Applications in Modern Systems

  • Traction systems (where legacy infrastructure still exists)
  • Test benches or laboratory setups needing two-phase power
  • HVDC converter stations (in some configurations)
  • Restoration of vintage industrial machines that use two-phase motors

10. Standards

Scott-T transformers generally follow the same core transformer standards:

  • IEC 60076 (Power Transformers)
  • IEEE C57 series
  • IS 2026 (Indian Standard for Power Transformers)