Technical Details – Scott-T Transformer
1. Overview
A Scott-T transformer is a special type of transformer arrangement used to convert three-phase electric power into two-phase power, and vice versa. It is named after Charles F. Scott, who introduced this method for phase conversion.
2. Applications
- Power supply to two-phase systems (e.g., older industrial machinery)
- Traction systems (railways with two-phase motors)
- Balancing unbalanced loads
- Interfacing two-phase legacy systems with modern three-phase grids
3. Basic Configuration
A Scott-T transformer uses two single-phase transformers:
- Main transformer
- Teaser transformer
Connection Details:
- The main transformer is connected between two phases (e.g., A and C) of a three-phase system.
- The teaser transformer is connected from the third phase (B) to a tap on the main transformer winding (typically at 86.6% or √3/2 of the winding).
Voltage Ratios:
- The teaser transformer's primary is 86.6% of the line voltage.
- The teaser’s secondary must be equal in voltage to the main transformer’s secondary to ensure balanced two-phase output.
4. Technical Specifications
Parameter
|
Typical Value
|
---|---|
Primary Voltage
|
3-phase, 50/60 Hz (e.g., 11 kV, 6.6 kV)
|
Secondary Voltage
|
2-phase output (e.g., 415 V-2Φ)
|
Frequency
|
50 or 60 Hz
|
Phase Shift
|
90° between two-phase outputs
|
Tap Position (Teaser)
|
50% to 86.6% from main’s neutral point (ideally at 0.866 × Vline)
|
5. Vector Representation
- The two-phase outputs are electrically 90° out of phase, forming a balanced two-phase system.
- The currents in the three-phase input remain balanced, if the two-phase loads are equal.
6. Design Considerations
- Magnetic coupling between windings is critical for maintaining phase relationships.
- Load balancing is important to avoid unbalanced current on the three-phase side.
- Proper tapping on the main transformer ensures correct voltage and phase angle.
7. Advantages
- Simple and cost-effective method for phase conversion.
- Allows integration of two-phase systems with standard three-phase grids.
- Provides balanced loading on the three-phase supply when used correctly.
8. Limitations
- Limited to specific use cases where two-phase supply is needed.
- Requires careful design to maintain voltage balance and phase angle.
- Less commonly used today due to the decline of two-phase systems.
9. Applications in Modern Systems
- Traction systems (where legacy infrastructure still exists)
- Test benches or laboratory setups needing two-phase power
- HVDC converter stations (in some configurations)
- Restoration of vintage industrial machines that use two-phase motors
10. Standards
Scott-T transformers generally follow the same core transformer standards:
- IEC 60076 (Power Transformers)
- IEEE C57 series
- IS 2026 (Indian Standard for Power Transformers)