Dry type VPI & Cast Resign Transformers

 Dry-Type Distribution Transformer – Technical Specifications

Distribution transformers are vital components in the electrical grid, used to step down high-voltage electricity from transmission lines to lower voltages suitable for commercial, industrial, and residential use. They are designed for high efficiency, safety, and long service life under varying load conditions.


 General Specifications

Parameter
Specification
Rated Power
25 kVA to 3000 kVA
Primary Voltage (HV)
11 kV / 22 kV / 33 kV
Secondary Voltage (LV)
11kV / 6.6kV / 3.6kV / 433 V (3-phase)
Frequency
50 Hz / 60 Hz
Phase
3-Phase (Standard)
Insulation Class
Class F / H
Cooling Type
AN (Air Natural), AF (Air Forced)
Enclosure Protection
IP23 / IP23 / IP34/ IP43 / IP56 
Standards
IS 2026 / IS 11171, IEC 60076-11, IEEE C57.12.01

 Electrical Characteristics

Feature
Details
Efficiency
≥ 98.5% (as per BEE/IS energy efficiency levels)
Impedance
Typically, 4% – 8.25%
Vector Group
Dyn11 (standard)
Tapping Range
±10% upto -20% @ 2.5% (Off-circuit Tap Links)
Losses
As per ECBC or Customer Specifications
Temperature Rise
≤ 90°C (winding), ≤ 150°C (hotspot)
Thermal Class
F (155°C) or H (180°C)
 

 Protection & Safety Features

Feature
Function
Over-temperature Protection
Thermistors / PT100 sensors with alarm and trip functions
Enclosure Options
VPI/VPE in IP-rated metal housing
Self-extinguishing Materials
Flame retardant insulation, non-toxic fumes
Low Noise Levels
Complies with IEC/IS sound level requirements
Seismic & Vibration Resistant
Suitable for critical installations (e.g., hospitals, airports)

 Applications

  • Commercial and Residential Buildings
  • Hospitals and Data Centers
  • High-rise Installations
  • Metro & Railway Infrastructure
  • Renewable Energy Systems (Indoor Use)