Technical Details – Compact Sub-station
A Compact Substation (CSS) is a prefabricated, factory-assembled unit that integrates medium-voltage (MV) switchgear, a distribution transformer, and low-voltage (LV) switchgear into a single, compact enclosure. Designed for rapid deployment and minimal spatial footprint, CSS units are ideal for urban, industrial, and infrastructure applications where space, safety, and reliability are paramount.
Technical Specifications of a Compact Substation
1. Transformer
- Type: Hermetically sealed oil-immersed or dry-type (cast resin) transformers.
- Power Rating: Upto 2500 kVA.
- Primary Voltage: Up to 33 kV.
- Secondary Voltage: 0.415 kV.
- Vector Group: Usually Dyn11.
- Impedance: Starting from 4.5%, depending on design.
2. Medium Voltage (MV) Switchgear
- Configuration: Ring Main Unit (RMU) or Vacuum Circuit Breaker (VCB) panels.
- Voltage Rating: 12 kV to 24 kV.
- Current Rating: Up to 630 A.
- Short-Circuit Rating: Up to 21 kA for 1 second.
- Insulation: SF6 gas-insulated or air-insulated options.
- Protection: Equipped with numerical relays for overcurrent and earth fault protection.
3. Low Voltage (LV) Switchgear
- Configuration: Air Circuit Breakers (ACB), Molded Case Circuit Breakers (MCCB), or fuse switches.
- Voltage Rating: 415 V.
- Current Rating: Up to 2500 A.
- Features: Includes metering devices, protection relays, and provision for Automatic Power Factor Correction (APFC) panels.
4. Enclosure
- Construction: Fabricated from CRCA or galvanized steel sheets, with thicknesses of 2 mm for load-bearing members and 1.5 mm for non-load-bearing members.
- Protection Class: IP54 for MV and LV compartments; IP23 for the transformer compartment.
- Surface Treatment: Powder-coated with UV-resistant finishes for outdoor durability.
- Compartments: Segregated sections for MV switchgear, transformer, and LV switchgear to enhance safety and ease of maintenance.
5. Standards Compliance
- IEC 62271-202: High-voltage/low-voltage prefabricated substations.
- IEC 60076: Power transformers.
- IEC 60439-1: Low-voltage switchgear and controlgear assemblies.
- IS 14786: Indian standard for prefabricated substations.
6. Additional Features
- Internal Arc Protection: Type-tested for internal arc faults up to 20 kA for 1 second, ensuring personnel safety.
- Cooling: Natural or forced ventilation systems, depending on transformer type and rating.
- Monitoring: Provision for temperature sensors, oil level indicators, and pressure relief devices.
- Earthing: Comprehensive internal earthing system connecting all metallic parts to a common earth point.
Typical Dimensions and Weight
Transformer Rating | Dimensions (L x W x H) mm | Approximate Weight (without equipment) |
---|---|---|
630 kVA | 2434 x 2134 x 2427 | 2700 kg |
1000 kVA | 2734 x 2134 x 2427 | 2775 kg |
1250 kVA | 3034 x 2434 x 2693 | 3400 kg |
1600 kVA | 3634 x 2434 x 2558 | 3400 kg |
Note: Dimensions and weights may vary based on specific designs and manufacturer specifications.
Applications
- Urban and Rural Distribution: Ideal for areas with space constraints.
- Industrial Facilities: Provides reliable power distribution for manufacturing units.
- Commercial Complexes: Ensures uninterrupted power supply for malls, offices, and hospitals.
- Renewable Energy Projects: Integrates seamlessly with solar and wind power installations.
- Infrastructure Projects: Suitable for airports, railways, and data centers.